Boiler Demineralized Water Treatment

 

Client: CHEMCHINA

Project: Boiler Demineralized Water Project

Capacity: 20,000 m³/D

Water Source: Yellow River Water

Application: Boiler demineralized water supply

page-300-250

 

Feed Water Quality Analysis

Parameter

Unit

Value

Conductivity

μS/cm

1215

COD

mg/L

4.22

Total Hardness

mg/L

262

Suspended Solids

mg/L

18.6

Turbidity

NTU

6-10

Chloride

mg/L

88

pH

-

7.8

Bicarbonate

mg/L

205

 

Ceramic Membrane Product Water Quality

Turbidity:<0.1 NTU

SDI (Silt Density Index): <3

Process Comparison

Original Process:

Yellow River Water → Reservoir → Chemical Pretreatment → Mechanical Filter → Ultrafiltration → Reverse Osmosis System

 

Upgraded Process (with Ceramic Membrane):

Yellow River Water → Reservoir → Ceramic Ultrafiltration System → Reverse Osmosis System

 

Key Advantages

 

Efficiency

The ceramic ultrafiltration membrane significantly reduces turbidity and SDI, ensuring stable feed water quality for downstream reverse osmosis.

 

Durability

Ceramic membranes withstand high turbidity and fouling, minimizing maintenance costs.

 

Cost Savings

Simplified pretreatment steps reduce operational complexity and energy consumption.

 

Outcome

The project successfully met CHEMCHINA's stringent requirements for boiler demineralized water, ensuring long-term operational reliability and compliance with industrial standards.